最近,筆者評審某設計時,發現電氣專(zhuan)業(ye)圖紙(zhi)僅有(you)文(wen)字(zi)說明“靜電接地(di)(di)見(jian)工(gong)(gong)(gong)(gong)藝專(zhuan)業(ye)示意(yi)”。而工(gong)(gong)(gong)(gong)藝專(zhuan)業(ye)的所有(you)設計文(wen)件,沒(mei)有(you)提到(dao)靜電接地(di)(di)的信(xin)息。工(gong)(gong)(gong)(gong)藝工(gong)(gong)(gong)(gong)程師給出“無論什么(me)管線均接地(di)(di)”。工(gong)(gong)(gong)(gong)程項目靜電接地(di)(di)設計沒(mei)有(you)完成,工(gong)(gong)(gong)(gong)藝的答復也不(bu)太合理。


  按(an)GB 50160必須靜電接地的介質管道如下。


   ①. 對爆炸、火災(zai)危險場(chang)所內可(ke)能產生(sheng)靜電危險的設(she)備和管道(dao),均應采取靜電接地措(cuo)施。


   ②. 在聚烯烴(jing)樹脂處理(li)系統、輸送(song)系統和料(liao)倉區應設置靜(jing)電接地系統,不(bu)得出現(xian)不(bu)接地的孤(gu)立導(dao)體(ti)。過去(qu)聚烯烴(jing)樹脂處理(li)、輸送(song)、摻混儲存系統由于靜(jing)電接地系統不(bu)完善,發生過料(liao)倉靜(jing)電燃(ran)爆事故。因此在物(wu)料(liao)處理(li)系統和料(liao)倉內嚴禁出現(xian)不(bu)接地的孤(gu)立導(dao)體(ti),如排風過濾器(qi)的緊固(gu)件、管道或軟(ruan)連接管的緊固(gu)件、振動篩的軟(ruan)連接、臨時接料(liao)的手推車或器(qi)具(ju)等。料(liao)倉內若有金(jin)屬凸出物(wu),必須做(zuo)防靜(jing)電處理(li)。


   ③. 可燃(ran)氣(qi)體、液(ye)化(hua)烴、可燃(ran)液(ye)體、可燃(ran)固(gu)體的(de)(de)管(guan)道在下列部位應設靜電接地設施:進(jin)出(chu)裝(zhuang)置或(huo)設施處(chu);爆(bao)炸危險(xian)場所(suo)的(de)(de)邊界;管(guan)道泵(beng)及泵(beng)入口永(yong)久(jiu)過濾器(qi)、緩沖器(qi)等(deng)。


   ④. 可燃液體、液化烴的(de)裝卸(xie)棧臺(tai)和(he)碼頭的(de)管(guan)道、設備(bei)、建筑物(wu)、構筑物(wu)的(de)金(jin)屬(shu)構件和(he)鐵路(lu)鋼軌等(deng)(作陰極保護者除外),均應做電氣連接(jie)并接(jie)地。


   ⑤. 汽車(che)罐車(che)、鐵路罐車(che)和(he)裝卸棧臺(tai)應(ying)設靜電專用(yong)接地(di)線。


   ⑥. 每(mei)組專設的靜電接地體的接地電阻值宜小于100Ω。


   ⑦. 除第一類防(fang)雷(lei)系(xi)統的獨立避雷(lei)針裝置的接(jie)地體(ti)外(wai),其(qi)他(ta)用(yong)途(tu)的接(jie)地體(ti),均(jun)可(ke)用(yong)于(yu)靜(jing)電接(jie)地。