工業企業對防靜電(dian)(dian)要(yao)求(qiu)較高,并不是所有(you)金屬(shu)管(guan)(guan)道法蘭(lan)(lan)必須全(quan)部跨(kua)接(jie)。是否(fou)需(xu)要(yao)跨(kua)接(jie)要(yao)看其設計文件是否(fou)有(you)靜電(dian)(dian)接(jie)地要(yao)求(qiu)。如果看不到設計文件,只能通(tong)過(guo)測量電(dian)(dian)阻(zu)值(zhi)的方式確定,當法蘭(lan)(lan)間(jian)電(dian)(dian)阻(zu)值(zhi)超過(guo)0.03Ω時(shi),需(xu)有(you)導線跨(kua)接(jie)。通(tong)過(guo)法蘭(lan)(lan)緊(jin)固(gu)方式或金屬(shu)螺(luo)栓數(shu)量來判定是否(fou)需(xu)要(yao)跨(kua)接(jie),適用于(yu)燃氣管(guan)(guan)道和石化(hua)企業內管(guan)(guan)道。管(guan)(guan)道法蘭(lan)(lan)跨(kua)接(jie)的常(chang)見規范要(yao)求(qiu)如下(xia)。


   ①. TSG D0001《壓力管(guan)(guan)(guan)道(dao)安全技(ji)術監察規(gui)程 工(gong)業管(guan)(guan)(guan)道(dao)》規(gui)定:有(you)靜電(dian)接(jie)地(di)要(yao)(yao)(yao)(yao)求的管(guan)(guan)(guan)道(dao),應(ying)當測量(liang)各連(lian)接(jie)接(jie)頭間的電(dian)阻(zu)值(zhi)(zhi)和管(guan)(guan)(guan)道(dao)系統(tong)的對地(di)電(dian)阻(zu)值(zhi)(zhi)。當值(zhi)(zhi)超(chao)過(guo)(guo)GB/T 20801《壓力管(guan)(guan)(guan)道(dao)規(gui)范 工(gong)業管(guan)(guan)(guan)道(dao)》或(huo)者設(she)計文件(jian)的規(gui)定時,應(ying)當設(she)置跨(kua)接(jie)導線(xian)(xian)(在法蘭或(huo)者螺紋接(jie)頭間)和接(jie)地(di)引線(xian)(xian)。由此可以看出,法蘭是否需(xu)要(yao)(yao)(yao)(yao)跨(kua)接(jie)導線(xian)(xian),需(xu)要(yao)(yao)(yao)(yao)測量(liang)法蘭之間電(dian)阻(zu)值(zhi)(zhi),當阻(zu)值(zhi)(zhi)超(chao)過(guo)(guo)規(gui)定時,需(xu)要(yao)(yao)(yao)(yao)跨(kua)接(jie)。


   ②. GB/T 20801《壓力管(guan)道規范 工業管(guan)道 第4部分 制作與安裝(zhuang)》規定:有靜電接地要(yao)求的(de)管(guan)道,各段間應導電良(liang)好。每對法(fa)蘭或螺(luo)紋接頭間電阻值(zhi)大(da)于(yu)0.03Ω時,應設導線跨(kua)接。


   ③. GB 50235《工業金屬管(guan)道(dao)施工及驗收規范(fan)》規定:有靜電(dian)(dian)接(jie)(jie)地(di)(di)要求(qiu)的管(guan)道(dao),各段間(jian)應導電(dian)(dian)良好。當每一對法蘭或螺紋(wen)接(jie)(jie)頭間(jian)電(dian)(dian)阻值大于0.03Ω時(shi),應有導線(xian)跨接(jie)(jie)。管(guan)道(dao)系統的對地(di)(di)電(dian)(dian)阻值超過100Ω時(shi),應設兩處接(jie)(jie)地(di)(di)引(yin)線(xian)。接(jie)(jie)地(di)(di)引(yin)線(xian)宜采用焊接(jie)(jie)形式。


   ④. GB 50517《石油化工金屬管道工程施工質量驗收規范(fan)》規定:有(you)靜電接地要(yao)求(qiu)的管道,當每對(dui)法蘭(lan)或螺紋接頭間電阻值大于0.03Ω時(shi),應有(you)導(dao)線跨接。


   ⑤. GB 50074《石(shi)油庫設計規(gui)范》規(gui)定(ding):輸油(油氣(qi))管道(dao)的法(fa)蘭連(lian)接處應跨接。當不(bu)少(shao)于5根螺栓連(lian)接時,在(zai)非腐蝕環境下可不(bu)跨接。


   ⑥. GB 50156《汽(qi)車加油(you)(you)加氣站設計與施工規范(fan)》規定(ding):在(zai)爆炸危險區域內的(de)油(you)(you)品、液化石油(you)(you)氣和天然氣管道上的(de)法蘭、膠管兩端等連接處應用(yong)金屬線跨接。當法蘭的(de)連接螺栓不少于5根時(shi),在(zai)非腐蝕(shi)環境下(xia),可不跨接。


   ⑦. SH 3097《石油化工靜(jing)電(dian)(dian)(dian)接(jie)(jie)地(di)(di)設計規(gui)(gui)范(fan)(fan)》作為企業規(gui)(gui)范(fan)(fan),嚴于國家標準和行業標準。該規(gui)(gui)范(fan)(fan)規(gui)(gui)定:在管(guan)道系統(tong)上,當(dang)金(jin)屬(shu)法蘭(lan)采(cai)用金(jin)屬(shu)螺栓(shuan)(shuan)或卡子緊固時,一(yi)(yi)般可不必另裝靜(jing)電(dian)(dian)(dian)連(lian)接(jie)(jie)線,但(dan)應保證至少有兩個螺栓(shuan)(shuan)或卡子間(jian)具有良好的(de)導(dao)電(dian)(dian)(dian)接(jie)(jie)觸面。有靜(jing)電(dian)(dian)(dian)接(jie)(jie)地(di)(di)要(yao)求(qiu)的(de)管(guan)道,各段間(jian)應導(dao)電(dian)(dian)(dian)良好。當(dang)每一(yi)(yi)對法蘭(lan)或螺紋接(jie)(jie)頭間(jian)電(dian)(dian)(dian)阻值大(da)于0.03Ω時,應有導(dao)線跨接(jie)(jie)。有靜(jing)電(dian)(dian)(dian)接(jie)(jie)地(di)(di)要(yao)求(qiu)的(de)不銹(xiu)鋼(gang)管(guan)道,導(dao)線跨接(jie)(jie)或接(jie)(jie)地(di)(di)引線應采(cai)用不銹(xiu)鋼(gang)板過渡,不得與不銹(xiu)鋼(gang)管(guan)直接(jie)(jie)連(lian)接(jie)(jie)。


   ⑧. SH 3501《石油化工劇毒、可燃(ran)介質管道(dao)工程施(shi)工及(ji)驗收(shou)規(gui)范》規(gui)定:有(you)靜(jing)電接地要求的管道(dao),各段間(jian)(jian)應導電良(liang)好(hao)。當每對法蘭或螺紋接頭間(jian)(jian)電阻值大于0.03Ω時,應有(you)導線跨接。


   ⑨. HG/T 23002《化工企業(ye)靜電(dian)安(an)全(quan)檢(jian)查規程(cheng)》作為靜電(dian)安(an)全(quan)檢(jian)查的(de)行業(ye)標準,規定:金屬設備與設備之間、管道與管道之間,如用金屬法蘭連接(jie)時可不另接(jie)跨接(jie)線,但必須有(you)兩個以(yi)上的(de)螺栓連接(jie)。



聯系方式.jpg