①. 城(cheng)市熱(re)力網管道(dao)(dao)應采用無(wu)縫鋼(gang)(gang)管、電(dian)弧焊(han)或高頻焊(han)焊(han)接鋼(gang)(gang)管。管道(dao)(dao)及鋼(gang)(gang)制(zhi)管件的(de)鋼(gang)(gang)材鋼(gang)(gang)號(hao)應不(bu)低于表8-8的(de)規(gui)(gui)定。管道(dao)(dao)和鋼(gang)(gang)材的(de)規(gui)(gui)格(ge)及質(zhi)量應符(fu)合國(guo)家相關標準的(de)規(gui)(gui)定。
②. 熱力(li)網(wang)凝(ning)結(jie)水管道(dao)宜(yi)采用(yong)具有防腐內襯(chen)、內防腐涂層的鋼管或(huo)非金屬管道(dao)。非金屬管道(dao)的承壓(ya)能力(li)和耐溫(wen)性能應滿(man)足設(she)計技術要(yao)求(qiu)。
③. 熱力網(wang)管(guan)(guan)道(dao)的連(lian)(lian)(lian)接(jie)應(ying)采(cai)(cai)用(yong)(yong)焊接(jie)。有條件時管(guan)(guan)道(dao)與設(she)備(bei)、閥(fa)門等(deng)連(lian)(lian)(lian)接(jie)也應(ying)采(cai)(cai)用(yong)(yong)焊接(jie),當需要拆(chai)卸時,采(cai)(cai)用(yong)(yong)法(fa)蘭連(lian)(lian)(lian)接(jie)。對公(gong)稱直徑小于(yu)或等(deng)于(yu)25mm的放氣(qi)閥(fa),可采(cai)(cai)用(yong)(yong)螺紋連(lian)(lian)(lian)接(jie),但連(lian)(lian)(lian)接(jie)放氣(qi)閥(fa)的管(guan)(guan)道(dao)應(ying)采(cai)(cai)用(yong)(yong)厚壁管(guan)(guan)。
④. 室(shi)外采(cai)暖計算(suan)(suan)(suan)溫度低(di)于-5℃地區(qu)露(lu)天敷設的不連續運(yun)行的凝結水(shui)管(guan)(guan)道放(fang)水(shui)閥門,室(shi)外采(cai)暖計算(suan)(suan)(suan)溫度低(di)于-10℃地區(qu)露(lu)天敷設的熱水(shui)管(guan)(guan)道設備附件均不得采(cai)用(yong)灰鑄鐵(tie)制品。室(shi)外采(cai)暖計算(suan)(suan)(suan)溫度低(di)于-30℃地區(qu)露(lu)天敷設的熱水(shui)管(guan)(guan)道,應采(cai)用(yong)鋼制閥門及附件。
⑤. 城(cheng)市(shi)熱(re)力網蒸汽管道(dao)在任(ren)何條(tiao)件(jian)下均應(ying)采(cai)用鋼制閥門(men)及附件(jian)。
⑥. 彎(wan)頭的壁厚(hou)應不(bu)小于管道壁厚(hou)。焊(han)接(jie)(jie)彎(wan)頭應雙面(mian)焊(han)接(jie)(jie)。
⑦. 鋼(gang)管(guan)(guan)焊制三(san)通,支管(guan)(guan)開(kai)孔應進行補(bu)強。對于(yu)承(cheng)受干管(guan)(guan)軸向(xiang)荷(he)載較大的直埋敷設管(guan)(guan)道(dao),應考慮三(san)通與管(guan)(guan)的軸向(xiang)補(bu)強,其技術要求按CJJ/T 81《城鎮直埋供熱管(guan)(guan)道(dao)工程(cheng)技術規(gui)程(cheng)》規(gui)定執行。
⑧. 變(bian)徑管(guan)制(zhi)作應采(cai)用壓制(zhi)或鋼(gang)板卷制(zhi),壁厚(hou)不應小于管(guan)道壁厚(hou)。