如圖8.2.16所示某蒸汽伴(ban)熱站,伴(ban)熱站包括分配(pei)(pei)站和疏水站。根(gen)據國內外標準規(gui)范的要(yao)求,分配(pei)(pei)站引(yin)出管(guan)(guan)根(gen)部閥(fa)(fa)A設(she)置(zhi)在(zai)距離總管(guan)(guan)盡量短的位置(zhi)。如果(guo)認(ren)為A處(chu)閥(fa)(fa)門(men)(men)(men)(men)在(zai)管(guan)(guan)廊高處(chu)不(bu)方便(bian)操作,移到了(le)距離地(di)面較(jiao)近的B處(chu)設(she)置(zhi)閥(fa)(fa)門(men)(men)(men)(men),當(dang)關(guan)閉(bi)B閥(fa)(fa)門(men)(men)(men)(men)時(shi)(shi)會(hui)造成死段(duan)較(jiao)長,引(yin)起(qi)管(guan)(guan)道死段(duan)腐蝕(shi)。如果(guo)A和B處(chu)均設(she)置(zhi)閥(fa)(fa)門(men)(men)(men)(men),需在(zai)B上部增加設(she)置(zhi)排液,避免同時(shi)(shi)關(guan)閉(bi)A和B處(chu)閥(fa)(fa)門(men)(men)(men)(men)時(shi)(shi)膨(peng)脹超壓;如果(guo)僅(jin)關(guan)閉(bi)B閥(fa)(fa)門(men)(men)(men)(men)而A閥(fa)(fa)門(men)(men)(men)(men)不(bu)關(guan)閉(bi),會(hui)引(yin)起(qi)管(guan)(guan)道死段(duan)腐蝕(shi)。因此,配(pei)(pei)管(guan)(guan)設(she)計時(shi)(shi)A和B處(chu)的閥(fa)(fa)門(men)(men)(men)(men),一般(ban)僅(jin)留A處(chu)的閥(fa)(fa)門(men)(men)(men)(men),B處(chu)一般(ban)不(bu)設(she)置(zhi)閥(fa)(fa)門(men)(men)(men)(men)。
伴熱站的疏水(shui)站根(gen)部閥(fa)(fa)門C的設計(ji)原理同A閥(fa)(fa)門。如果C處凝結水(shui)返回(hui)管(guan)口徑≥2”,凝結水(shui)返回(hui)管(guan)應(ying)順流向(xiang)方向(xiang)45°斜(xie)接到凝結水(shui)總管(guan)。配管(guan)設計(ji)要求和(he)原理詳細講述見《管(guan)道(dao)應(ying)力分析與工(gong)程(cheng)應(ying)用(yong)》、《壓力管(guan)道(dao)設計(ji)及工(gong)程(cheng)實例(li)》和(he)《工(gong)業管(guan)道(dao)配管(guan)設計(ji)與工(gong)程(cheng)應(ying)用(yong)》。