①. 變(bian)電(dian)、配電(dian)室是散(san)發(fa)火花地點,是裝置的動力中心,屬于(yu)重(zhong)點保護建(jian)筑物,其(qi)位置盡可能設在便于(yu)引接(jie)電(dian)源、接(jie)近負(fu)荷中心和進出線方便之(zhi)處,避免設在有(you)劇烈振(zhen)動的場所。
②. 變電(dian)、配(pei)電(dian)室一般不與可燃氣體壓縮機共用(yong)(yong)一幢建筑(zhu)物,常與控(kong)制室共用(yong)(yong)一幢建筑(zhu)物。對于用(yong)(yong)電(dian)量較大的裝置往(wang)往(wang)變電(dian)、配(pei)電(dian)室設在獨立的建筑(zhu)內(nei)。
③. 變壓器可露天(tian)或半(ban)露天(tian)布置,這時變壓器周(zhou)圍(wei)應設固(gu)定圍(wei)欄,變壓器外廊與圍(wei)欄或建筑物墻的距離不(bu)應小于0.8m。
④. 電(dian)(dian)(dian)纜(lan)(lan)(lan)(lan)敷(fu)設(she)方式有兩種,即(ji)電(dian)(dian)(dian)纜(lan)(lan)(lan)(lan)溝敷(fu)設(she)和架空(kong)敷(fu)設(she)。有的裝置兩種方式均采用(yong),即(ji)從配電(dian)(dian)(dian)室(shi)地(di)下溝內引電(dian)(dian)(dian)纜(lan)(lan)(lan)(lan)至用(yong)電(dian)(dian)(dian)設(she)備區,對于泵和壓縮機的驅動(dong)機用(yong)電(dian)(dian)(dian)纜(lan)(lan)(lan)(lan)一般(ban)仍采用(yong)溝內敷(fu)設(she),對于架空(kong)設(she)備或設(she)施如空(kong)冷器、檢修用(yong)固定(ding)式吊(diao)車和照明電(dian)(dian)(dian)纜(lan)(lan)(lan)(lan)則采用(yong)架空(kong)敷(fu)設(she),這樣比(bi)較(jiao)經(jing)濟合(he)理。
⑤. 變(bian)電、配電室(shi)(shi)還(huan)需要(yao)一間(jian)維修值班室(shi)(shi)。