①. 電(dian)伴(ban)熱(re)系統安裝(zhuang)前,被伴(ban)熱(re)管道必(bi)須全(quan)部(bu)施工完畢,并經水壓試驗、氣密試驗檢查合格。


  ②. 安裝時,應先(xian)按照電(dian)伴熱系統圖(tu)逐(zhu)一核對管(guan)道編號、管(guan)道規格、工藝條件、電(dian)伴熱參(can)數、規格型(xing)號、電(dian)氣設備和控制設備規格型(xing)號等確認無(wu)誤后(hou)才(cai)能安裝。


  ③. 電(dian)(dian)(dian)伴(ban)熱帶或電(dian)(dian)(dian)纜線有良好的柔(rou)性(xing)(xing),不得(de)(de)硬折,需(xu)要彎曲時,其曲率半徑不得(de)(de)小(xiao)于電(dian)(dian)(dian)熱電(dian)(dian)(dian)纜外(wai)徑或自(zi)限性(xing)(xing)電(dian)(dian)(dian)熱帶厚度的6倍。


  ④. 電伴(ban)熱(re)帶(dai)或(huo)電纜應與(yu)被(bei)伴(ban)熱(re)管(guan)道(dao)或(huo)設備(bei)貼(tie)緊(jin),并用扎帶(dai)固定;對于非金(jin)(jin)屬管(guan)道(dao),應在管(guan)外壁與(yu)伴(ban)熱(re)帶(dai)之(zhi)間(jian)夾一金(jin)(jin)屬片(pian)(鋁箔),以提高傳(chuan)熱(re)效果。


  ⑤. 電(dian)伴熱(re)(re)帶(dai)(dai)和電(dian)熱(re)(re)電(dian)纜的安裝(zhuang)如(ru)圖13.20所示。一般在管(guan)道(dao)(dao)的側下方(fang),當(dang)遇到(dao)法蘭(lan)時,由于法蘭(lan)處(chu)易發(fa)生泄漏,應避開其正(zheng)下方(fang);當(dang)設置多根電(dian)熱(re)(re)帶(dai)(dai)時,按互成90°分(fen)布或等(deng)距離(li)布置,每隔300~600mm應有扎帶(dai)(dai),扎帶(dai)(dai)材料應根據管(guan)道(dao)(dao)溫度選用。


  ⑥. 電伴熱(re)系統(tong)安裝完畢(bi)后(hou),必須逐個(ge)回路進行電氣測試,合(he)格后(hou)再進行通電試驗,檢查發現情況,處理正常后(hou)方可(ke)保(bao)溫。


  ⑦. 電(dian)熱(re)電(dian)纜是制造(zao)廠根據用(yong)戶的有關條件(jian)專(zhuan)門制作(zuo)的,因此不能互相代用(yong);安(an)裝時不得重疊、交(jiao)叉和(he)搭接,不得剪(jian)斷。


  ⑧. 電熱電纜的接頭處附近80mm左右不得彎(wan)曲,在接頭兩側應有扎帶(dai)。


20.jpg



典(dian)型部位的電伴(ban)熱設(she)計(ji)


  典型(xing)部位的電伴(ban)熱安(an)裝(zhuang)示意圖(tu)見圖(tu)13.21。